Power 864SECURITY SYSTEM®TMInstallation ManualIMPORTANTThis manual contains information on limitations regarding product use and function and informat
5Telephone Connection Terminals - TIP, RING, T-1, R-1If a telephone line is required for central station communication or downloading, connect an RJ-3
6System Outputs (all 12 VDC)Other DevicesRead the manufacturer’s literature carefully to determine the maxi-mum current requirement (during activation
Installation and Wiring: 2.9 Removing Modules7In LED keypads, zone lights will be turned on according to what modules the panel has found on the syste
8Fire Zone Wiring - 4-wire Smoke DetectorsAll zones defined as Fire (see section 5.3 Basic Programming PWS Sect 3 on page 17) must be wired according
9Section 3: How to ProgramThe following section of the manual describes how to enter Installer Programming and how to program the various sections.NOT
10Section 4: Keypad CommandsUse any system keypad to enter commands, or to program the Power864 security system. The LED keypad uses function and zone
11A bypassed zone will not cause an alarm. Instructions on zone bypassing can be found in the Power864 Instruction Manual (“Zone Bypassing”). When the
12[✱] [3] Alarm MemoryThe ‘Memory’ light will be on if any alarm occurred during the last armed period or if an alarm occurred while the panel was dis
Keypad Commands: 4.3 Function Keys13Scroll to the day of the week you want to change, or enter the number of the day (1-7 for Sunday to Saturday). On
14select Partition 1 (see section 4.4 Global and Partition Keypad Opera-tion on page 15).[02] - Select Partition 2Provides an easy way to select Parti
New FeaturesPC5200 SupportThe PC5020 v3.1 supports the new PC5200 Power Supply module. See PC5200 Power Supply Output Module, Pg 2.PC5936 Support The
Keypad Commands: 4.4 Global and Partition Keypad Operation154.4 Global and Partition Keypad OperationA global keypad will display limited information
16Section 5: Programming SectionsThe structure of this section corresponds with the structure of the Programming Worksheets (PWS) and is intended to b
Programming Sections: 5.1 For the Record PWS Sect 1175.1 For the Record PWS Sect 1This Section identifies the Client, Installation Date, Installers Co
18[005] - System TimesThis section has 9 sub-sections, 1 for each of the 8 partitions, and 1 for the Bell timeout. A 2-digit entry is required to acce
19[006] - Installer’s Code. Installer Lockout Enable . . . . . . . . . . . . . . . . . . . . . . Section [990]Installer Lockout Disable . . . . . .
2010 Latched System Event (Strobe). This output will activate when any of the selected system events (alarms) occur on the system. In the armed state,
Programming Sections: 5.3 Basic Programming PWS Sect 321[012] - Keypad Lockout OptionsThe panel can be programmed to ‘lockout’ keypads if a series of
22Option Definition On/Off Description2 Bell During Auto-ArmON Bell Squawk During Auto-Arm Enabled. The Bell output will sound a single squawk every 1
Programming Sections: 5.3 Basic Programming PWS Sect 323Option Definition On/Off Description7 Telephone Line Monitor ON Telephone Line Monitor enabled
24Option Definition On/Off Description3 Audible RF Jam Trouble BeepsON Audible RF Jam Trouble BeepsOFF An RF Jam will not sound Trouble Beeps4 Double
PC5020 Installer Programming Quick Reference Chart SIA False Alarm ReductionMinimum requirement system for SIA-FAR Installations :• 1 PC5020 Control p
Programming Sections: 5.3 Basic Programming PWS Sect 325Option Definition On/Off Description2 Verbal Door Chime ON Verbal Door Chime is Enabled. The s
26[020] - Keypad Zone Assignment Assigning Keypad ZonesEach keypad has a zone input to which a device (i.e. a door contact) can be connected. (See Sec
Programming Sections: 5.5 Partition & Zone Programming27occurs after this timer expires, the Police Code will not be logged or transmitted, and th
28Telephone numbers can be up to 32 digits which will allow you to add special digits if required. To program the telephone number enter numbers 0 thr
Programming Sections: 5.6 Communicator Programming PWS Sect629Alarm Canceled: this reporting code will be sent if a valid access code is entered durin
30General System Trouble Restoral: a General System Trouble Restoral Reporting Code will be transmitted when the panel detects none of the following:
Programming Sections: 5.6 Communicator Programming PWS Sect631SIA Sends Automatic Reporting Codes . . .Section [381], Option [3]Communicator Call Dire
32This section requires 2 two digit entries (1 per phone number). The 3rd telephone number uses the format programmed for the 1st tele-phone number.Re
Programming Sections: 5.6 Communicator Programming PWS Sect633[378] - Test Transmission Time of DayProgram the time of the test transmission in this s
347 LINKS Dialing ON Call LINKS as well as Land-line(s). The control panel will dial the programmed number of attempts through the LINKS, followed by
iTable of ContentsSection 1: Introduction 11.1 About the Power864 System ... 11.2 About the Power864 Manual Set
35 [390]-[393] LINKS PreamblesDownloading can be performed through the LINKS1000 cellular communicator if the telephone line is disconnected. If usin
36Redundant CommunicatorThe panel can be programmed to call using the land line and the LINKS1000 cellular communicator when an event occurs. To progr
37[402] - Downloading Computer’s Telephone NumberThis telephone number is 32 digits in length. [403] - Downloading Access CodeThis 4-digit Hexadecimal
38[551]-[564] PGM Partition AssignmentThe PC5020 has a 8-bit toggle field per output that determines which partitions the output is assigned to (outp
Programming Sections: 5.10 Module Programming PWS Sect 1039[703] - Delay Between Dialing AttemptsFor standard (force) dialing, the panel will go off-h
40Periodic Camera TestWhen the Periodic Camera Test option is enabled, the panel will test cameras connected to a PC5108L module every 30 minutes. Onl
Programming Sections: 5.11 Special Installer Instructions PWS Sect 1141[991][Installer Code] - Installer Lockout DisableThis disables the Installer Lo
42Appendix A: Reporting CodesThe following tables contain Contact ID and Automatic SIA format reporting codes. For more information on reporting code
Reporting Codes43Section # Reporting Code Code Sent When...Dialer Direction*Automatic Contact ID CodesSIA Auto Rep Codes**[344] Special Opening Openin
44Table2: Contact ID Zone Alarm/Restoral Event Codes (as per ADEMCO):Program any of these codes for zone alarms/restorals when using the standard (non
iiPC5020 Wiring DiagramNOTE: AUX+ (420mA) isshared between AUX+,Keybus and all PGM outputsWARNING: Not to be removed by anyone except occupant. This e
FCC COMPLIANCE STATEMENTCAUTION: Changes or modifications not expressly approved by DigitalSecurity Controls Ltd. could void your authority to use thi
WARNING Please Read CarefullyNote to InstallersThis warning contains vital information. As the only individual in contact with system users, it is you
NOTESWWW.DIYALARMFORUM.COM
©2001 Digital Security Controls Ltd., Toronto, Canadawww.dsc.com Printed in Canada 29005882 R001 PC5020 Module CompatibilityModule Compatible? Comm
1Section 1: Introduction1.1 About the Power864 SystemThe Power864 is a high end security system. It supports up to 64 zones, 8 separate partitions, an
2False Alarm Prevention Features• Audible Exit Delay• Audible Exit Fault • Urgency on Entry Delay• Quick Exit• Swinger Shutdown• Recent Closing Transm
Introduction: 1.4 Additional Devices3For more information on either module, see their respective installa-tion manuals.NOTE: The PC5108L module can o
4Section 2: Installation and WiringThe following sections provide a complete description of how to wire and configure devices and zones.2.1 Installati