PC5020 Installer Programming Quick Reference Chart
SIA False Alarm Reduction
Minimum requirement system for SIA-FAR Installations :
1 PC5020 Control panel
2 Local annunciation devices
The local annunciation devices may be any combination of the following keypads.
LCD5500Z
PKP-LCD
LCD5501Z
•PKP-ICN
The following optional subassembly modules also bear the SIA FAR classification
and may be used if desired:
PC5132-433 Receiver Module
Compatible initiating devices: WLS-912-433, WLS904PL-433, WLS914-433, and
WLS-925-433
PC5108 Zone Expander Module
Compatible Initiating devices: Bravo 200series, 300series, 400series, 500series,
600 series, AC-100, Encore 300series, Force 200series, 210series, MN240
PC5100 2-wire Addressable Loop Interface Module
Compatible Initiating devices: AMB-300, 500, 600, AMA-100, AMP-700,
701,702
PC5208 Low Current PGM Output Module
PC5204 Auxiliary Power Supply with PGM output ports
Escort5580/Escort5580TC
PC5400 Printer Module
Caution
Wireless smoke detectors (WLS906-433) cannot be employed in conjunc-
tion with the PC5132-433 Wireless receiver for SIA FAR Installations.
Addressable smoke detectors (AMS220, AMS220T) cannot be employed
in conjunction with the PC5100 Addressable loop module for SIA FAR
Installations.
Fire Alarm Verification feature (Auto Verified Fire zone) is not supported
on Two wire smoke detectors zones. This feature may be enabled for 4
wire smoke detectors only.
Call Waiting Cancel (Section 382 Option 4) feature on a non -Call Wait-
ing line will prevent successful communication to the central station.
Notes
Programming at Installation may be subordinate to other UL require-
ments for the intended application.
Unvacated premises: When the system/partition is armed in Stay Mode
and the exit delay time expires, the system will automatically Away Arm.
This will function properly, provided that the premises are not exited via a
Delay 1 or Delay 2. There must be a minimum of one Stay/Away or Delay
Stay/Away zone enrolled on the partition.
Cross-zones have the ability to individually protect the intended area (ex.
motion detectors, which overlap).
Cross zoning is not recommended for Line security Installations nor is it to
be implemented on exit / entry zones.
There is a Communication Delay of 30 seconds in this control panel. It
can be removed, or it can be increased up to 45 seconds at the option of
the end user by consulting with the Installer.
Do not duplicate any reporting codes. This applies for all communication
formats other than SIA sending automatic programmed reporting codes.
Section Number Installation
Manual Section
Description
005 5.3 System Times: Access to Entry Delays and Exit Delay for each partition and Bell Time Out for the system.
009 – 011 5.3 Programmable Outputs: Access to PGM Output programming for the main board, PC5208 and PC5204 modules. Output
Attributes in Section in Sections 501 – 514. Partition Assignments in Section 551 – 564.
014, Option 6 5.3 Audible Exit Beeps: Enables beeps from the keypad for the duration of Exit Delay.
018, Option 6 5.3 Cross Zoning: Enables Cross Zoning for the entire system. Individual zones can be enabled for Cross zoning via Zone
Attributes in Sections 101 – 164.
018, Option 7 5.3 Exit Delay Restart: Enables the Exit Delay Restart feature.
101 – 164 5.4 Zone Attributes: Access to zone attributes, such as, Audible Bell, Swinger Shutdown, Transmission Delay, and Cross
Zone.
176 5.4 Cross Zone Timer: Access to the programmable Cross Zone timer.
304 5.6 Call Waiting Cancel Dialing String: Access to the Dialing sequence used to disable Call Waiting.
328, 6
th
Entry
5.6 Cross Zone Reporting Code: Access to the reporting code for Cross Zone Alarm.
328, 7
th
Entry
5.6 Burglary not Verified Reporting Code: Access to the reporting code for Burglary Not Verified.
328, 8
th
Entry
5.6 Alarm Cancelled Reporting Code: Access to the reporting code for Alarm Cancelled.
348, 1
st
and 2
nd
Entries
5.6 Walk Test End and Begin Reporting Codes: Access to the reporting codes for Walk Test Begin and Walk Test End.
377, 1
st
Entry
5.6 Swinger Shutdown for Alarms: Access to the Swinger Shutdown limit for zone alarms.
377, 4
th
Entry
5.6 Communications Delay: Access to the programmable delay before communicating alarms.
377, 11
th
Entry
5.6 Communications Cancel Window: Access to the programmable Communications Cancel window.
382, Option 2 5.6 Alarm Comms. During Walk Test: Enables Communication of zone alarms while installer Walk Test is active.
382, Option 3 5.6 Communications Cancelled Message: Enables the “Communications Cancelled” message display on all keypads.
382, Option 4 5.6 Call Waiting Cancel: Enables the use of the Call Waiting Cancel string in programmed in Section 304.
901 5.11 Installer Walk Test Mode: Enable/Disable Installer Walk Test mode. This mode can be used to test each zone on the sys-
tem for proper functionality.