3
Fire Zone Wiring
Any one of the 6 zones may be programmed as a Fire Zone.
See Programming Guide Section [11].
Smoke detectors should be the latching type and have N.O.
alarm initiating contacts. Power wiring from the AUX + /
PGM terminals should be supervised using an RM-1 relay
after the last smoke detector. The RM-1 N.O. contacts
(closed with power applied) should be wired in series with
the alarm initiating end-of-line resistor so that should power
to the detector(s) fail, a fire zone trouble will be initiated.
AWG AWG AWG AWG AWG AWG
14 16 18 19 22 24
19 800' 12 450' 7800' 6200' 3000' 1900'
6035m 3794m 2377m 1889m 914m 579m
Figures based on maximum loop resistance of 100 ohms.
Alarm Initiating Loop Wiring Chart
Wire
Gauge
Distance
to EOL
Resistor
Max. Wire Run to E.O.L. Relay
AWG AWG AWG AWG AWG
14 16 18 19 22
4750' 3000' 1880' 1500' 750'
1447m 914m 573m 457m 228m
2375' 1500' 940' 750' 370'
723m 457m 286m 228m 112m
1190' 750' 470' 370' 180'
362m 228m 143m 112m 56m
790' 500' 310' 250' 120'
240m 152m 94m 76m 36m
595' 375' 235' 185' 90'
181m 114m 71m 56m 27m
Current
mA
50
100
200
300
400
Wire run distances are in feet/meters from the Aux. +/- terminals to
the End-Of-Line Power Supervisory Relay. Figures are based on 12
VDC at the Aux +/- terminals with a maximum 10% voltage drop at
the RM-1 relay.
Fire Zone Power Wiring Chart
Burglary Zone Wiring
Burglary zone definition, (eg. Delay, Instant, 24 Hr. etc.) is
programmed via the keypad. See the Programming Guide,
Section [11].
Zone Wiring Chart
Figures based on maximum loop
resistance of 100 ohms.
Wire Gauge Max. Run Length to
(AWG) End-of-Line resistor
24 1900’ (579m)
22 3000’ (914m)
20 4900’ (1493m)
19 6200’ (1889m)
18 7800’ (2377m)
AC Power Wiring
Complete all wiring to the control panel before connecting AC
power or the battery. Do not plug the transformer into an
outlet that is controlled by a switch.
Battery Connection
If the battery is reverse connected, the 5 A fuse will blow. The
battery charging voltage is factory set and normally needs no
adjustment. If the battery charging voltage is out of adjustment,
contact your service representative.
If AC power is OFF and the battery voltage is approximately
9.5 V or lower, the battery will be disconnected and the panel
will power down. To power up again, the AC will have to be
re-established.
Telephone Line Wiring
Do not connect the alarm panel communicator to
telephone lines intended for use with facsimile (fax)
machines. These lines may incorporate a voice filter
which disconnects the line if other than fax signals are
detected. This may result in incomplete transmissions
from the alarm panel communicator.
AUX +
PGM
Z1
COM
DETECTOR
POWER
12VDC
IN
OUT
N.O.
ALM
-
OUT
+
-
IN
+
BLK WHT
RED GRN
LATCHING 4-WIRE
SMOKE DETECTOR
1k 0.5W
END OF LINE
RESISTOR
RM-1 POWER LOOP
SUPERVISORY RELAY
12VDC 35mA MAX.
WHT
ALARM INITIATING
LOOP; RESISTANCE 100