Strobe Output (Latched Alarm Output)
WI
The PGM switches to ground on an alarm and remains low until the panel is disarmed. It can be used
to indicate that an alarm has occurred before entering the premises.
Failure to Communicate
The PGM output switches to ground if the system fails to communicate after 8 attempts to each phone
number that will be tried according to Section [25] Communicator Call Direction Options. The output
remains low until a successful communication takes place or until the Unsuccessful Communication
Attempt trouble is cleared. This option can be used to link two systems together so that if one fails to
communicate, the other system will report the failure.
~251
Communicator Call Directions
Section [25] determines how the communicator will call the telephone numbers programmed in Sections
[Ol]
and [03] to report the following events:
l Zone Alarms and Restorals
l Access Codes Openings and Closings
l Priority Alarms and Restorals
l Maintenance Alarms and Restorals
Enter one digit from the list below for each of the reporting groups. The default setting is [I] for all groups.
[0] No transmission
[1]
Call 1st phone number and back-up to the 2nd phone number when Section [13] Light 1 is OFFand the
panel has made 8 unsuccessful attempts on the 1st phone number.
[2] Call the 2nd phone number only
[3] Always call both phone numbers
NOTE: If the [#] Key is pressed during data entry, the keypad will return to the Installer’s Programming Mode
and any data entered in this section will not be saved.
[2g]
Downloading Telephone Number
Enter the Downloading Telephone Number in this section. This telephone number is dialled during automatic
downloading or when downloading is requested with the
[$][4]
command. RefertoSection
[I
4],3rd
System Option
Code, Lights 2and 3.
Referto
Section
[Ol]
1st Phone
Number
for
instructionson programming telephone numbers.
1271
Downloading Access Code
This 4-digit code allows the panel to confirm that it is communicating with the intended downloading computer.
Enter 4 digits using the numbers 0 through 9 only. The default code is [1515].
[281
Panel Identification Code
This 4-digit code allows the downloading computer to confirm the identity of the control panel. Enter 4 digits
using the number keys 0 through 9 only. The default code is [1501].
I291
Number of Rings Sefore Answering
Section [29] sets the number of rings before the panel will pick-up the line and answer the call.
Refer to Section
[31]
for information on using the system with an answering machine connected to the same phone line.