DSC PC 5010 Installation Manual Page 54

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 53
48
Appendix A: Reporting Codes
The following tables contain Contact ID and Automatic
SIA format reporting codes. For more information on
reporting code formats and notes about individual
reporting codes,
(see section 5.6 ‘Communicator Pro-
gramming’ PWS Sect 6).
Contact ID
The first digit (in parentheses) will automatically be sent
by the control panel. The second two digits are pro-
grammed to indicate specific information about the sig-
nal. For example, if zone 1 is an entry/exit point, you
could program the event code as [34]. The central station
would receive the following:
*BURG - ENTRY/EXIT - 1 where the ’1’ indicates which
zone went into alarm.
SIA Format - Level 2 (Hardcoded)
The SIA communication format used in this product fol-
lows the level 2 specifications of the SIA Digital Commu-
nication Standard - October 1997. This format will send
the account code along with its data transmission. The
transmission will look similar to the following at the
receiver:
N Ri01 BA 01
N= New Event
Ri01 = Partition /Area Identifier
BA = Burglary Alarm
01 = Zone 1
NOTE:
A system event will use the Area Identifier Ri00.
Section # Reporting Code Code Sent When...
Dialer
Direction*
Automatic
Contact ID
Codes
SIA Auto Rep
Codes**
[320]-[321] Zone Alarms Zone goes into alarm A/R See Table 3 See Table 3
[324]-[325] Zone Restorals Alarm condition has been restored A/R
[328] Duress Alarm Duress code entered at keypad A/R (1) 21 HA-00
[328] Opening After Alarm System disarmed with alarm in memory A/R (4) A6 OR-00
[328] Recent Closing Alarm occurs within two minutes of system arming A/R (4) 59 CR-00
[328] Zone Expander Supervisory
Alarm/Rest.
Panel loses/restores supervisory transmission over the Keybus
from zone expansion modules, or keypads with zone inputs
A/R (1) 43 UA-00/UH-00
[328] Cross Zone (Police Code)
Alarm
Two zones on the same partition go into alarm during any given
armed-to-armed period (incl. 24-hr zones)
A/R (1) 39 BM-00/BV-00
[328] Burglary Not Verified This reporting code will be sent after the Burglary Verified Timer
expires after a zone alarm occurs.
A/R (3) 78 BG-00
[328] Alarm Cancelled This reporting code will be sent if a valid access code is entered
during the Alarm Cancel window
A/R (4) A6 BC-00
[329] [F] Key Alarm/Restoral Keypad fire alarm (alarm and restoral reporting codes sent
together)
A/R (1) 15 FA-00/FH-00
[329] [A] Key Alarm/Restoral Keypad auxiliary alarm (alarm and restoral reporting codes sent
together)
A/R (1) AA MA-00/MH-00
[329] [P] Key Alarm/Restoral Keypad panic alarm (alarm and restoral reporting codes sent
together)
A/R (1) 2A PA-00/PH-00
[329] Aux Input Alarm/Restoral
Option#23/24
: a panic button wired to PGM 2 is pressed/
access code is entered
Option #04:
a 2-wire smoke detector wired to PGM 2 goes
into alarm/alarm is cleared.
A/R
A/R
(1) 4A
(1) 11
UA-99/UH-99
FA-99/FH-99
[330]-[335] Zone Tamper/Restoral Zone is tampered / Tamper condition restored T/R (1) 44 TA-ZZ/TR-ZZ
[338] General System Tamper/Rest. Enrolled module with tamper inputs has a Tamper alarm/all
module Tampers restored
T/R (1) 45 TA-00/TR-00
[338] Keypad Lockout Maximum number of incorrect access codes has been entered
at a keypad
T/R (4) 21 JA-00
[339-341] Closings System armed (user 01-34, 40-42 indicated) O/C (4) A2 CL-UU
[341] Partial Closing One or more zones bypassed when system armed O/C (4) 7A CG-ZZ
[341] Special Closing Closing (arming) using one of the following methods: quick
arm, auto-arm, keyswitch, function key, maintenance code, DLS
software, wireless key
O/C (4) AA CL-00
[341] Late to Close Whenever the auto-arm pre-alert sounds (if the Late to Close
option is enabled)
O/C (4) A4 CI-00
[341] Exit Fault When Exit Fault Pre-Alert occurs and Entry Delay expires before
the system is disarmed
O/C (4) 57 EE-00
[342-344] Openings System disarmed (user 01-34, 40-42 indicated) O/C (4) A2 OP-UU
[344] Auto-arm Cancellation Auto-arm cancelled O/C (4) A5 CE-00
* A/R = alarms/restorals; T/R = tampers/restorals; O/C = openings/closings; MA/R = miscellaneous alarms/restorals; T = test transmissions
** UU = user number (user01-42); ZZ = zone number (01-32)
Page view 53
1 2 ... 49 50 51 52 53 54 55 56 57 58 59 60