DSC PC 5010 Installation Manual Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
6
Keybus Terminals - RED, BLK, YEL, GRN
The Keybus is used by the panel to communicate with
modules and by modules to communicate with the panel.
Each module has four Keybus terminals that must be con-
nected to the four Keybus terminals on the panel. For
more information, see section ’Keybus Operation and
Wiring
.
Programmable Outputs PGM1, PGM2
Each PGM output is designed so
that when activated by the panel,
the terminal will switch to ground
PGM1 can sink up to 50 mA of
current. These PGMs can be used
to activate LEDs or a small buzzer.
Connect the positive side of the
LED or buzzer to AUX+, the nega-
tive side to the PGM.
PGM2 is a high current output
(300mA) and operates similarly to
PGM1. If more than 300 mA of cur-
rent is required, a relay must be
used. PGM2 can be used for 2-wire smoke detectors with
Jumper CON1 removed, otherwise, CON1 must remain on
at all times (see section 2.10 ‘Zone Wiring‘).
Zone Input Terminals - Z1 to Z8
Each detection device must be connected to a zone on the
control panel. It is suggested that each zone have one
detection device however it is possible to wire multiple
detection devices to the same zone.
For zone wiring specifics, see section ’Zone Wiring’
.
Telephone Connection Terminals - TIP, RING, T-1, R-1
If a telephone line is required for central station commu-
nication or downloading, connect an RJ-31X jack in the
following manner:
Connect the PC5010 CP-01 and modules that use the tele-
phone line(s) in the following order:
For example, if you are installing a PC5010 CP-01 with a
LINKS1000/GSM1000 and a PC5936 intercom module,
connect the incoming line to the LINKS1000, then from
the LINKS1000 to the PC5010 CP-01, then from the
PC5010 CP-01 to the PC5936 audio module and then from
the PC5936 module to the house telephones.
NOTE:
Ensure that all plugs and jacks meet the dimension,
tolerance and metallic plating requirements of 47 C.F.R. Part
68, SubPart F. For proper operation there must be no other
telephone equipment connected between the control panel
and the telephone company facilities.
NOTE:
Do not connect the alarm panel communicator to
telephone lines intended for use with a FAX machine. These
lines may incorporate a voice filter which disconnects the
line if anything other than FAX signals are detected, result-
ing in incomplete transmissions.
2.3 Wire Routing for Power & Non-Power Limited
All wiring entry points are designated by the arrows. All
circuits are classified UL installation power limited except
for the battery leads which are not power limited.
A minimum ¼” (6.4mm) separation must be maintained
at all points between power limited and non-power lim-
ited wiring and connections.
NOTE:
Wire entry for power limited wiring must be sepa-
rated by a different entry access from non-power limited
wiring.
2.4 Keybus Operation and Wiring
The Keybus is used by the panel to communicate with all
modules connected and by the modules to talk to the
panel. The RED and BLK terminals are used to provide
power while YEL and GRN are clock and data.
NOTE:
The 4 Keybus terminals of the panel must be con-
nected to the 4 Keybus terminals or wires of all modules.
The following conditions apply:
Keybus should be run in minimum 22 gauge quad
(0.5mm), two pair twisted preferred
the modules can be home-run to the panel, connected in
series or can be T-tapped
any module can be connected anywhere along the Key-
bus; you do not need a separate Keybus wire run for
keypads, zone expanders etc.
no module can be more than 1,000'/305m (in wire
length) from the panel
shielded wire is not necessary unless wires are run in an
area that may present excessive RF noise or interference
Example of Keybus Wiring
Module (A) is wired cor-
rectly as it is within 1,000'/
305m of the panel, in wire
distance. Module (B) is
wired correctly as it is
within 1,000'/305m of the
panel, in wire distance.
Module (C) is NOT wired
correctly as it is further than 1,000'/305m from the panel,
in wire distance.
2.5 Current Ratings - Modules & Accessories
In order for the PC5010 CP-01 system to operate properly,
the power output capabilities of the main control and
expansion devices must not be exceeded. Use the data
presented below to ensure that no part of the system is
overloaded and cannot function properly.
PC5936
PC5010
TIP2
RNG2
TIP1
RNG1
TIP
RNG
TIP
RNG
T-2
R-2
T-1
R-1
T-1
R-1
T-1
R-1
TIP
RNG
T-1
R-1
TIP
RNG
T-1
R-1
TIP
RNG
T-1
R-1
Line 2 from
Telephone Company
Line 1 from
Telephone Company
To premise
Telephones
To premise
Telephones
Keybus
NOTE: A minimum 1/4" (6.4mm) separation
must be maintained at all points between
power limited and non-power limited wiring
and connections.
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 59 60

Comments to this Manuals

No comments