Programming Sections:
5.3 Basic Programming PWS Sect 3
21
[005] - System Times
This section has 3 sub-sections, 1 for each of the 2 parti-
tions, and 1 for the Bell time-out. A 2-digit entry is
required to access these sub-sections.
NOTE:
Entry of 000 in these sections will result in a 255- sec-
ond time.
Sub-Sections 1-2 each require three 3-digit entries.
[01] - [
[01] - [[01] - [
[01] - [02
0202
02]
]]
] Entry Delay 1, Entry Delay 2, and Exit Delay
per partition.
•Entry Delay 1:
Entry Delay 1:Entry Delay 1:
Entry Delay 1: 030-240 Seconds
This value determines the Entry delay time for Delay 1
type zones. The default Entry Delay 1 time is 30 seconds.
•Entry Delay 2:
Entry Delay 2:Entry Delay 2:
Entry Delay 2: 030-240 Seconds
This value determines the Entry delay time for Delay 2
type zones. The default Entry Delay 2 time is 30 seconds.
•Exit Delay:
Exit Delay:Exit Delay:
Exit Delay: 045-255 Seconds
This value determines the Exit delay time when arming
the system. The default Exit Delay time is 60 seconds.
NOTE:
The Exit Delay must not exceed 255 seconds. The
minimum possible entry is 45 seconds.
NOTE:
If the Exit Delay is silent (Section 014, Option 6 or
Stay Function Key Arming) the Exit Delay will be twice the
programmed value (060-510 seconds).
[09] Bell Time-out:
[09] Bell Time-out:[09] Bell Time-out:
[09] Bell Time-out: 001-255 Minutes
The Bell Time-out for all 2 partitions will be the same.
The siren will silence after the number of minutes pro-
grammed for the Bell Time-out
Bell Time-out Bell Time-out
Bell Time-out value has passed. The
default Bell Time-out is 4 minutes
The panel supervises the Bell output. If an open condition
is detected, the panel will immediately indicate a Trouble
condition by beeping the keypad twice every 10 seconds
to alert the owner to the problem. The panel can send a
Bell Circuit Trouble
Bell Circuit Trouble Bell Circuit Trouble
Bell Circuit Trouble and Trouble Restoral
Trouble Restoral Trouble Restoral
Trouble Restoral reporting codes
to indicate the situation (see section 5.6, ‘Communicator
Programming’ PWS Sect 6).
If the Temporal Three Fire Signal
Temporal Three Fire Signal Temporal Three Fire Signal
Temporal Three Fire Signal option is enabled, all
Fire signals will follow the Temporal Three Pattern as
described in NFPA 72. If turned OFF all Fire signals will
sound a one second on, one second off cadence.
If Fire Bell Continuous
Fire Bell Continuous Fire Bell Continuous
Fire Bell Continuous is enabled, the alarm output will
sound until a code is entered. If disabled, the alarm will
sound until a code is entered or the bell time-out has
expired.
NOTE:
Only fire zones will follow the Temporal Three Fire
Signal.
Bell Time-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [005]
Bell Circuit Trouble Reporting Code . . . . . . . . . . . . . . Section [345]
Bell Circuit Trouble Restoral Reporting Code. . . . . . . . Section [346]
Temporal Three Fire Signal
Enable/Disable . . . . . . . . . . . . . . . . . . . . . Section [013], Option [8]
Fire Bell Continuous . . . . . . . . . . . . . . . . . Section [014], Option [8]
25 Interior Delay Zone
The Interior Delay Zone is normally used with motion detectors and has a standard Exit Delay time. If the panel is
armed, and a Delay zone is violated during the Exit Delay (or the Away function key is used), the Interior Delay Zone
will be active at the end of the Exit Delay. This zone will cause an instant alarm when violated. This zone type will fol-
low the Entry Delay time provided that a Delay zone is violated first. If the panel is armed, and a Delay zone is NOT
violated during the Exit Delay (or the Stay function key is used, or [*][9] armed), a violation of this zone type will ini-
tiate Entry Delay 1.
26 24-hr Non-Alarm
These zones are active at all times but do not cause an alarm, and do not show up in alarm memory. Zone Attributes
such as Zone Bypassing and Door Chime affect the functionality of this zone. A 24-hr Non-alarm zone may be used
for Zone Follower automation applications.
NOTE: This zone type will be active in Walk Test. Tampers and Faults. Zones programmed as 24-hr Non-
alarm type will not cause alarms.
NOTE: Alarms on this zone will not initiate Downlook.
27 Delayed 24-hr Water-
flow
These zones will follow the waterflow Delay Timer. When a delayed waterflow zone is violated, the waterflow timer
will start, (any subsequent delayed waterflow zones that become active do not reset or abort this timer). If there are
still delayed waterflow zones open when the waterflow timer expires, the panel will go into alarm and communicate
the event(s) regardless of the armed state.
28 Instant 24-hr Water-
flow
A waterflow alarm is a Fire alarm. The Fire related bells and Aux functions are activated. This Zone type functions
similar to Type 27 (Delayed 24-hr waterflow), but does not follow the Waterflow Delay Timer. When this zone is vio-
lated, it will immediately go into alarm. This zone type always uses a single EOL configuration.
29 Auto Verified Fire Zone
This zone ensures that an alarm condition persists by resetting a tripped sensor in a fire zone and confirming that the
sensor has remained tripped or is waiting for the sensor to re-trip within a set period of time (e.g., cycling power to
a smoke detector to ensure the condition persists when power is restored). The alarm sequence for the zone is indi-
cated below:
Step #1 Duration 20 Seconds Sensor Reset
Step #2 Duration 10 Seconds Settle Time (Power-up)
Step #3 Duration 60 Seconds Check for Verified Alarm
NOTE: If another Fire device detects Fire during the Auto Verify or Delay sequence, the sequence is termi-
nated and alarms are immediately generated for all pending zones. This applies to all other Fire zones on
the system regardless of the partition assignments (i.e., two fire alarms anywhere on the system will can-
cel all pending fire delays and create immediate alarms).
30 Fire Supervisory Zone
When this zone is violated, the system turns on the keypad buzzer, and communicates the supervisory alarm condi-
tion to the monitoring station. The buzzer will not follow the Bell Time-out. To silence the buzzer, a valid access code
must be entered.
NOTE: The fire supervisory alarm is not affected by the waterflow silence inhibit option described in
[018], Option 4, Pg 32
31 Day Zone
A zone programmed as this type has different characteristics in the armed and disarmed state. In the disarmed state,
violating this zone will sound the keypad buzzer but will not log or report the event. In the armed state, violating this
zone will sound the bell and communicate the event.
87 Delayed 24-hr Fire
(Wireless)
Used only with wireless smoke detectors. Functions same as Zone Type [07].
88 Standard 24-hr Fire
(Wireless)
Used only with wireless smoke detectors. Functions same as Zone Type [08].
[001]-[002] ZONE DEFINITIONS