PC5010 CP-01 Installer Programming Quick Reference Chart SIA False Alarm Reduction
Minimum requirement system for SIA-FAR Installations :
1 PC5010 CP-01 Control Panel
2 Local Annunciation Devices
The local annunciation devices may be any combination of the following keypads.
LCD5500Z/LCD5520Z LCD5501Z
PKP-LCD PKP-ICN
The following optional subassembly modules also bear the SIA FAR classification
and may be used if desired:
PC5108 Zone Expander Module
Compatible initiating devices: Bravo200 series, 300 series, 400 series, 500 series,
600 series, AC-100, Encore300 series, Force200 series, 210 series, MN240.
PC5208 Low Current PGM Output Module
The following optional accessory modules also bear the SIA FAR classification and
may be used if desired.
PC5204 Auxiliary Power Supply with PGM output ports
Escort5580/Escort5580TC
PC5400 Printer Module
Caution
• For SIA FAR installations, only use modules / devices that are listed
on this page.
• Fire Alarm Verification feature (Auto Verified Fire zone) is not sup-
ported on 2-wire smoke detectors zones. This feature may be
enabled for 4-wire smoke detectors only.
• Call Waiting Cancel (Section 382 Option 4) feature on a non-Call
Waiting line will prevent successful communication to the central
station.
• All smoke detectors on the system must be tested annually by con-
ducting the Installer Walk Test. Prior to exiting the walk test mode,
a sensor reset must be conducted on the system, [*][7][2] to reset
all latching 4-wire smoke detectors. Please refer to the smoke
detector installation instructions on how to correctly test the detec-
tors.
Notes
Programming at installation may be subordinate to other UL require-
ments for the intended application.
Cross zones have the ability to individually protect the intended area
(e.g., motion detectors, which overlap).
Cross zoning is not recommended for line security Installations nor is it to
be implemented on exit / entry zones.
There is a communication delay of 30 seconds in this control panel. It can
be removed, or it can be increased up to 45 seconds at the option of the
end user by consulting with the Installer.
Do not duplicate any reporting codes. This applies for all communication
formats other than SIA sending automatic programmed reporting codes.
The control unit must be installed with a local sounding device and an
off-premise transmission for SIA communication format.
Section Number Installation
Manual Section
Description
005 5.3 System Times: Access to Entry Delays and Exit Delay for each partition and Bell Time Out for the system.
009 – 011 5.3 Programmable Outputs: Access to PGM Output programming for the main board, PC5208 and PC5204 modules. Output
Attributes in Section in Sections 501 – 514. Partition Assignments in Section 551 – 532.
014, Option 6 5.3 Audible Exit Beeps: Enables beeps from the keypad for the duration of Exit Delay.
018, Option 6 5.3 Cross Zoning: This option enables Cross Zoning for the entire system. Individual zones can be enabled for Cross zoning
via Zone Attributes in Sections 101 – 132. Default = OFF
018, Option 7 5.3 Exit Delay Restart: Enables the Exit Delay Restart feature.
101 – 132 5.4 Zone Attributes: Access to zone attributes, such as, Audible Bell, Swinger Shutdown, Transmission Delay, and Cross Zone.
176 5.4 Cross Zone Timer: Access to the programmable Cross Zone timer.
304 5.6 Call Waiting Cancel Dialing String: Access to the Dialing sequence used to disable Call Waiting.
328, 6
th
Entry
5.6 Cross Zone Reporting Code: Access to the reporting code for Cross Zone Alarm.
328, 7
th
Entry
5.6 Burglary not Verified Reporting Code: Access to the reporting code for Burglary Not Verified.
328, 8
th
Entry
5.6 Alarm Cancelled Reporting Code: Access to the reporting code for Alarm Cancelled.
348, 1
st
and 2
nd
Entries
5.6 Walk Test End and Begin Reporting Codes: Access to the reporting codes for Walk Test Begin and Walk Test End.
377, 1
st
Entry
5.6 Swinger Shutdown for Alarms: Access to the Swinger Shutdown limit for zone alarms.
377, 4
th
Entry
5.6 Communications Delay: Access to the programmable delay before communicating alarms.
377, 11
th
Entry
5.6 Communications Cancel Window: Access to the programmable Communications Cancel window.
382, Option 2 5.6 Alarm Comms. During Walk Test: Enables Communication of zone alarms while installer Walk Test is active.
382, Option 3 5.6 Communications Cancelled Message: Enables the “Communications Cancelled” message display on all keypads.
382, Option 4 5.6 Call Waiting Cancel: Enables the use of the Call Waiting Cancel string in programmed in Section 304.
901 5.11 Installer Walk Test Mode: Enable/Disable Installer Walk Test mode. This mode can be used to test each zone on the sys-
tem for proper functionality.
[*][5] Master Code
33rd and 34th Entries
4.1 Duress Code: Do not derive code from an existing Master/User code (eg., Master Code is 1234, the duress code should
not be 1233 or 1235.
[*][6] Master Code
Option 4
4.3 System Test: The system activates all keypad sounders, bells or sirens for 2 seconds and all keypad lights turn on. Refer
to the User Manual (part no. 29005909).