Communicator Programming
17
[378] Test Transmission Time of Day
Default
9999 I_______I_______I_______I_______I
Valid entries are 0000-2359, 9999 to disable)
NOTE: Do not enter [9999] for Central and Remote Fire Applications.
Communicator Options
[380] First Communicator Option Code
Default Option ON OFF
ON
I_______I 1 Communications Enabled Communications Disabled
OFF
I_______I 2 Restorals on Bell Time-out Restorals Follow Zones
OFF
I_______I 3 Pulse Dialing DTMF Dialing
OFF
I_______I 4 Switch to Pulse Dialing on 5th Attempt DTMF Dial For All Attempts
OFF
I_______I 5 3rd Telephone Number enabled 3rd Telephone Number disabled
OFF
I_______I 6 Alternate Dial (1st and 3rd) Call 1st Number, Backup to 3rd
OFF
I_______I 7 Call LINKS as well as Land Line LINKS is Backup of Land Line(s)
OFF I_______I 8 Delinquency Follows Zone Activity (Hours) Delinquency Follows Arming (Days)
[381] Second Communicator Option Code
Default Option ON OFF
OFF
I_______I 1 Open After Alarm Kypd Ringback enabled Open After Alrm Kypd Ringback disabled
OFF
I_______I 2 Open After Alarm Bell Ringback enabled Open After Alrm Bell Ringback disabled
OFF
I_______I 3 SIA Sends Programmed Rep. Codes SIA Sends Automatic Rep. Codes
OFF
I_______I 4 Closing Confirmation Enabled Closing Confirmation Disabled
ON
I_______I 5 Talk/Listen (PC5936) on phone lines 1/3 No Talk/Listen (PC5936) on phone lines 1/3
OFF
I_______I 6 Talk/Listen (PC5936) on phone line 2 No Talk/Listen (PC5936) on phone line 2
ON
I_______I
7 Contact ID Uses Programmed Rep. Codes Contact ID Uses Automatic Rep. Codes
OFF I_______I 8 Local Mode Enabled Local Mode Disabled
[382] Third Communicator Option Code
Default Option ON OFF
OFF
I_______I 1 Contact ID. Partial Closing Identifier is 5 Partial Closing ID is 4
OFF
I_______I 2 Alarm Communications Enabled During Walk Test* Alarm Communications Disabled During Walk Test
ON
I_______I 3 Communication Cancelled Message Enabled Communication Cancelled Message Disabled
OFF
I_______I 4 Call Waiting Cancel Enabled** Call Waiting Cancel Disabled
OFF
I_______I 5 T-Link Interface Enabled*** T-Link Interface Disabled
OFF
I_______I 6 AC Failure Transmission Delay is in Hours† AC Failure Transmission Delay is in Minutes
OFF
I_______I 7-8 For Future Use
*This option must remain OFF for SIA-FAR installations.
** A Call Waiting Cancel on a non-Call Waiting line will prevent successful connection to the central station.
***T-Link Interface not investigated by UL.
For central and remote fire applications, this option must be ON.
LINKS1000 Preambles
NOTE: Do not use this section for central and remote fire applications.
[390] LINKS1000 Preamble (First Telephone Number)
Default: FFFF I_______I_______I_______I_______I
(Program all unused digits with Hex F)
[391] LINKS1000 Preamble (Second Telephone Number)
Default: FFFF
I_______I_______I_______I_______I
(Program all unused digits with Hex F)
[392] LINKS1000 Preamble (Third Telephone Number)
Default: FFFF I_______I_______I_______I_______I
(Program all unused digits with Hex F)
[393] LINKS1000 Special Function Preamble (All Telephone Numbers)
Default: FFFFFF
I_______I_______I_______I_______I_______I_______I
(Program all unused digits with Hex F)
• Enter [*][2][*] (HEX B) to dial [*]
• Enter [*][3][*] (HEX C) to dial [#]