DSC PC4020 - V3.3 Installation Manual Page 52

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 51
48
Appendix A: Reporting Codes
Notes on Contact ID
The following is a list of Contact ID reporting codes. The
first digit (in parentheses) will automatically be sent by
the control. The last two digits are programmed to indi-
cate specific information about the signal.
For example, if zone 1 is an entry/exit point, the alarm
reporting code could be programmed as [34]. The central
station would receive the following:
*BURG - ENTRY/EXIT - 1
In the above example, the ’1’ indicates the zone in alarm.
Notes on SIA Format
If the SIA 1 Account # option is selected, the panel will
send the system account code along with its data trans-
mission (ref # [000401], scroll to option). At the receiver,
the transmission would look similar to this example:
N Ri01 / BA 001
N= New Event
Ri01 = Partition /Area Identifier
BA = Burglary Alarm
001 = Zone 1
4-Digit Reporting Codes
When using 4-digit reporting codes a leading zero will be
added to all reporting codes except for the user numbers
(0000 to 1500).
* A/R = alarms/restorals; O/C = openings/closings; O = other
** PPP = partition number; UUU = user number (user 1000 to 1500 = 999); ZZZ = zone number
Ref. # Reporting Code Code Sent When...
Dialer
Direction*
Contact
ID
SIA Auto Rep
Codes**
[00040300] Zone Alarms zone goes into alarm A/R
see Appendix B ’Zone
Reporting Codes’
[00040301] Zone Restorals alarm condition has been restored A/R
[00040302] Zone Trouble/Tamper zone exhibits a trouble/tamper condition A/R
[00040303] Zone Trouble/Tamper Rest. trouble/tamper condition has cleared A/R
[00040304] Zone Fault zone exhibits a zone fault A/R
[00040305] Zone Fault Rest. zone fault condition has cleared A/R
[00040306] [F] Key Alarm/Rest. Keypad fire alarm (alarm and restore rep.
codes sent together)
A/R (1) 15 FA-000/FH-000
[00040306] [A] Key Alarm/Rest. Keypad auxiliary alarm (alarm and restore rep.
codes sent together)
A/R (1) AA MA-000/MH-
000
[00040306] [P] Key Alarm/Rest. Keypad panic alarm (alarm and restore rep.
codes sent together)
A/R (1) 2A PA-000/PH-000
[00040307] Duress Alarm Duress code entered A/R (1) 21 HA-000
[00040307] Opening After Alarm partition disarmed with alarm in memory A/R (4/5) 58 OR-000
[00040307] Recent Closing alarm occurs within two minutes of partition
arming
A/R (4) 59 CR-000
[00040307] Cross Zone (Police Code)
Alarm
two zones on the same partition go into
alarm within the Police Code Time during any
given armed period (incl. 24Hr zones)
A/R (1) 39 BV-000
[00040307] Door Forced Alarm/Rest. (access control) door forced open alarm event
occurs (PC4820 only)
A/R (1) NONE DF-ZZZ/DR-ZZZ
[00040307] Door Open Too Long Alarm/
Rest.
(access control) door open too long events
occur (PC4820 only)
A/R (1) NONE DN-ZZZ/DH-ZZZ
[00040307] Alarm Cancel a user presses the Cancel function key after
the partition has gone into alarm
A/R (4) A6 BC-UUU
[00040308] General System Tamper/Rest. enrolled module with tamper inputs has a
tamper alarm
O (1) 45 TA-000/TR-000
[00040309] Keypad Lockout max. number of incorrect access codes has
been entered at a keypad
O (4) 21 JA-000
[00040309] 2-wire Alarm/Rest. 2-wire smoke alarm (PC4701 only) A/R (1) 11 FA-999/FH-999
[00040309] Waterflow Alarm/Rest. waterflow zone alarm (PC4701 only) A/R (1) 13 SA-998/SH-998
[00040309] 2-wire Trouble/Rest. 2-wire smoke zone has a trouble (open) condi-
tion (PC4701 only)
A/R (3) 73 FT-999/FJ-999