DSC PC4020 - V3.3 Installation Manual Page 49

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 48
45
Section 16: Diagnostics and Troubleshooting
16.1 General Diagnostics
Ref #: [04]
The diagnostics function is designed to help you track
down any problems with the installed modules.
If there is no problem the keypad will display ’PC40X0 Sys-
tem No Faults Found’.
If there is a problem, the keypad will display ’Error... Mod-
ule’. This message will be accompanied by either ’E’ ’T’ or
’LV’ followed by a number. The number represents the
module (see list below). The letters represent the following:
E = communications error. The main panel has lost com-
munications with the module.
• T = tamper. The tamper zone on the module has been
activated.
• LV = low voltage. The module is not receiving enough
voltage from the Combus.
Below is a list of the indicated numbers and which mod-
ules they represent.
Indicated #Module #
1-8 For Future Use
9-24 LCD45XX - #1-16
25-28 PC440X - #1-3
29-44 PC41XX - #1-16
45-53 PC4216 - #1-9
54-69 PC4204/PC4204CX - #1-16
70 Not used
71 ESCORT4580
72-87 PC4820 - #1-16
88 PC4701
89-92 PC4702 #1-4
93 PC4936
94-109 PC4850 #1-16
110 Alt. Comms
16.2 Restoring Factory Default Programming
These options are only available during the first 10 min-
utes after power up. To access these sections, disconnect
then reconnect the AC and battery power. Then, enter [*]
[8] [Installers Code], followed by reference number [0402]
to default the main panel, or [0403] to default the
ESCORT4580 (if installed).
Factory Default (Software)
Ref #: [0402]
Once this selection has been made, the keypad will read
’Confirm Default Press *’. Press the [*] key to confirm the
operation. To cancel the default, press the [#] key.
Once the [*] key is pressed, the programming keypad will
display the message ’Power System Down and Restart’.
Remove the battery and AC connections to the control
panel. This will erase all programming and reset the sys-
tem to its factory default settings. All modules will have to
be re-enrolled.
When using AML devices, the AML Key will return to
[00] upon resetting the panel’s software.
Default ESCORT4580 (if installed)
Ref #: [0403]
Once this selection has been made, the keypad will read
’Confirm Default Press *’. Press the [*] key to confirm the
operation. To cancel the default, press the [#] key.
Once the [*] key is pressed, the programming keypad will
display the message ’Resetting 4580 Module’. Once the
default is complete, the keypad will display ’4580 Default
is Complete’. The ESCORT4580 module will be reset to its
factory default settings.
16.3 Hardware Reset
If the installer’s code is lost inadvertently, the only way to
reprogram the system is to perform a hardware reset.
NOTE: If the Installer’s Lockout feature is enabled,
there is no way to reprogram the system without enter-
ing the correct installer’s code. Panels returned to the
manufacturer with this feature enabled and exhibiting
no other problems will be subject to an additional ser-
vice charge.
NOTE: Delete any enrolled AML zones from the system
before performing a Hardware Reset.
To reset the panel to its factory default settings, perform
the following:
1. Power the system down by removing both the AC con-
nections and the battery power to the control panel.
2. Short the Z1 and PGM1 terminals on the control panel.
Nothing else should be connected to Z1 or to the PGM
terminals.
3. Restore power to the control panel. Wait for 20 seconds.
4. Power down the panel by removing both the AC and
battery connections.
5. Remove the short between the Z1 and PGM1 terminals.
The system will have reloaded all factory default set-
tings. All modules will have to be enrolled again. The
event buffer is the only part of the system’s memory
that will not be restored.
6. Power up the panel. Connect the battery first, then
the AC.
16.4 Viewing Trouble Conditions
The alarm control panel continuously monitors a number
of possible trouble conditions. If one of these conditions
occurs, the keypad Trouble light will turn on and a beep-
ing sound will be heard every 10 seconds. Press the [#] key
to silence the keypad. The Trouble light will stay on until
the trouble is cleared.
If the Audible AC Tbl option is turned on (ref # [000200]),
keypads will sound trouble beeps at the end of the AC Fail
Delay (see 10.9 ‘Transmission Delay‘) when the panel loses
AC power. If the option is turned off, keypads will not
sound trouble beeps when the panel loses AC power. The
option is off by default.
If the Latch Troubles option is turned on (ref # [000200]),
whenever any panel or module AC or battery trouble
Page view 48